| Plan Review Notes For Permit 00031559 |
| Permit Number |
00031559 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE "AO". WILL NEED TO PROVIDE | | | AN ELEVATION CERTIFICATE. | | | 2-REVISE AGAIN THE ATTIC ACCESS PANEL | | | SIZE. MINIMUM SIZE IS 22"X36" AS PER | | | SECTION 2309.6 SBC 1997. | | | 3-UPDATE/REVISE DRAWINGS AS REQUIRED: | | | -PROVIDE REAR ELEVATION AND FLOOR PLAN | | | THAT MATCH TABLE 600 CALCULATIONS. | | | 4-PROVIDE PRODUCT APPROVAL FOR ENTRY | | | DOORWITH SIDELITE AND PLEASE MAKE | | | SURE DRAWINGS ARE LEGIBLE. | | | 5-SLIDING GLASS DOORS BY NORANDEX: | | | PROVIDE COPIES OF TESTS RESULTS DONE | | | AS PER ASTM E-330. | | | SECTION 1706 SBC 1997. |
|