| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-SOIL TEST REPORT CALLS FOR 18" MIN. |
| | WIDTH OF FOOTING. REVISE AS RQUIRED. |
| | 2-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| | "INSWING" DOORS, EXTERIOR FRENCH DOOR |
| | AT MASTER SUITE. |
| | 3-REVISE/UPDATE PLANS. SEE COMMENTS ON |
| | PLANS. |
| | 4-PROVIDE ATTIC ACCESS AT MAIN ROOF. |
| | SECTION 2309.6 SBC 1997. |
| | 5-ENGINEERED ROOF TRUSSES: |
| | -MEAN ROOF HEIGHT IS 18'-6" PLUS OR |
| | MINUS. MEAN ROOF HEIGHT IS TAKEN FROM |
| | GRADE, NOT FROM FINISH FLOOR, TO THE |
| | AVERAGE POINT OF HIGHEST ROOF. |
| | -UPDATE ALL GENERAL DETAILS USING SBC |
| | 1997 OR ASCE 7-95. SIGNED, SEALED AND |
| | DATED BY ENGINEER WHO PREPARED THEM. |
| | 6-SPECIFY CEILING CONSTRUCTION AT FRONT |
| | AND REAR PORCHES. INCLUDE FASTENERS |
| | TYPE AND SPACING. SEC 2504 SBC 1997. |
| | 7-ENGINEER WHO SIGNED AND SEALED DESIGN |
| | CERTIFICATION FOR BUILDING CODE |
| | COMPLIANCE FORM TO SIGN AND SEAL ALL |
| | STRUCTURAL DRAWINGS AS WELL. |
| | 8-STORM PANELS: |
| | -PROVIDE A COMPLETE INSTALLATION SCHED, |
| | AS PER CITY SAMPLE, AND KEY PLAN. |
| | CLEARLY SPECIFY MOUNTING METHOD AND |
| | ANCHOR AND SPACING TO BE USED |
| | ACCORDING TO THE DESIGN PRESSURES, |
| | PANEL SPAN, EDGE DISTANCE AND BUILDING |
| | CONSTRUCTION TYPE. |
| | NOTE: USING CONCRETE VALUES FOR STORM |
| | PANELS ATTACHED TO CONCRETE BLOCK |
| | COLUMNS WITH FILLED CELLS ARE NOT |
| | ACCEPTABLE. |