| Plan Review Notes For Permit 00031481 |
| Permit Number |
00031481 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT A STORM WATER RISER THAT CLEARLY | | | SHOWS THE ENTIRE STORM SYSTEM BEING | | | INSTALLED AT THIS TIME.SHOW THE SQUARE | | | FOOT AREA BEING DRAINED BY EACH DRAIN & | | | NOTE ENTIRE SQUARE FOOT AREA OF ROOF. | | | SYSTEM SHALL BE SIZED PER SPC TABLES | | | 1108.1,1108.2. | | | | | | OVERFLOW DRAINS SHALL BE SIZED PER SPC | | | SEC.1109.3. | | | | | | WHERE DO ROOF DRAINS TERMINATE? DRAINS | | | COLLECTING CONDENSATE SHALL NOT | | | DISCHARGE OVER SIDEWALK. | | | | | | REVISE SHT.274U-1 TO REFLECT ALL CORRECT | | | CHANGES TO PLAN.(SQ.FOOT AREA DRAINED BY | | | ROOF DRAINS) |
|