2001-01-08 00:00:00SUBMIT A STORM WATER RISER THAT CLEARLY
 SHOWS THE ENTIRE STORM SYSTEM BEING
 INSTALLED AT THIS TIME.SHOW THE SQUARE
 FOOT AREA BEING DRAINED BY EACH DRAIN &
 NOTE ENTIRE SQUARE FOOT AREA OF ROOF.
 SYSTEM SHALL BE SIZED PER SPC TABLES
 1108.1,1108.2.
  
 OVERFLOW DRAINS SHALL BE SIZED PER SPC
 SEC.1109.3.
  
 WHERE DO ROOF DRAINS TERMINATE? DRAINS
 COLLECTING CONDENSATE SHALL NOT
 DISCHARGE OVER SIDEWALK.
  
 REVISE SHT.274U-1 TO REFLECT ALL CORRECT
 CHANGES TO PLAN.(SQ.FOOT AREA DRAINED BY
 ROOF DRAINS)