Plan Review Notes
Plan Review Notes For Permit 00031481
Permit Number 00031481
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT COMPLETE SANITARY AND WATER
 SUPPLY RISER DIAGRAMS FOR REVIEW FOR ALL
 CHANGES TO THE PLUMBING SYSTEM PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SHT.274M-1-TERMINATION OF CONDENSATE
 DRAINS SHALL COMPLY W/COUNTYWIDE AMEND-
 MENTS TO SPC SEC.804.3.
  
 SUBMIT COPY OF JOB SPECS AS REFERENCED
 ON PLANS.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 SHT.274U-1-PLANS SHOW 2 ROOF DRAINS
 DRAINING 18000 & 18750 SQ.FT.EACH AND
 ROOF AREA IS TOTAL OF 18000 SQ.FT.-
 CLARIFY.