| Plan Review Notes For Permit 00031481 |
| Permit Number |
00031481 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************8 UNSAT **************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | MAINS! 110-9/215-5 MAINS ARE TO BE RATED | | | FOR THE AVAILABLE FAULT CURRENT. | | | | | | 2)NOTE: PLEASE SUBMIT PLANS SHOWING THE | | | GFI PROTECTION REQ`ED BY 230-95 | | | PLEASE INDICATE VOLTAGE ON SERVICE. | | | 215-5 | | | 3)NOTE: PLEASE SHOW WIRE SIZES BEING | | | INSTALLED OR NOTE IF THEY ARE BEING IN- | | | STALLED AT LATER DATE. | | | | | | PLEASE NOTE THAT ALL REVISIONS THAT ARE | | | BROUGHT IN ARE TO BE CLOUDED OR TRIANGL- | | | ES. REVISIONS ARE TO BE ATTACHED TO ALL | | | PLANS THAT ARE ALREADY IN FOR REWIEW(BY | | | THE CONTRACTOR) ALL OLD PAGES NEED TO | | | COME OUT FOR NEW CLEAN SETS TO BE REVIEW | | | -ED. | | | PLEASE NOTE THAT THERE IS NOT ENOUGH | | | INFORMATION FOR AN INTERIOR BUILD OUT | | | REVIEW. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS | | | -E CALL 659-8096 EXT 8372 |
|