2001-01-08 00:00:00***************8 UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 MAINS! 110-9/215-5 MAINS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOTE: PLEASE SUBMIT PLANS SHOWING THE
 GFI PROTECTION REQ`ED BY 230-95
 PLEASE INDICATE VOLTAGE ON SERVICE.
 215-5
 3)NOTE: PLEASE SHOW WIRE SIZES BEING
 INSTALLED OR NOTE IF THEY ARE BEING IN-
 STALLED AT LATER DATE.
  
 PLEASE NOTE THAT ALL REVISIONS THAT ARE
 BROUGHT IN ARE TO BE CLOUDED OR TRIANGL-
 ES. REVISIONS ARE TO BE ATTACHED TO ALL
 PLANS THAT ARE ALREADY IN FOR REWIEW(BY
 THE CONTRACTOR) ALL OLD PAGES NEED TO
 COME OUT FOR NEW CLEAN SETS TO BE REVIEW
 -ED.
 PLEASE NOTE THAT THERE IS NOT ENOUGH
 INFORMATION FOR AN INTERIOR BUILD OUT
 REVIEW.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 -E CALL 659-8096 EXT 8372