2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT PLANS SHOWING ALL
 NEW CIRCUTS WITH BRANCH CIRCUT #`S.
 THIS INCLUDES LIGHTING.
  
 2)NOTE:PLEASE SUBMIT NEW LOAD CALCULAT-O
 -ION OF EXISTING SERVICE. REVISE PANEL
 SCHEDULE.
  
 3)NOTE: ALL LIGHTING LOADS ARE TO BE
 FIGURED AT 125 % FOR CONTINUOUS LOAD.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372