| Plan Review Notes For Permit 00031388 |
| Permit Number |
00031388 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1)FORM 600 A-97 OF ENERGY CODE LISTS | | | 3726 S.F.OF CONDITIONED FLOOR AREA AND | | | SHEET C-1 OF PLANS LIST AREA UNDER AIR | | | AS 3513 S.F.; CLARIFY | | | | | | 2)SHEET A-5 SPECIFIES R-30 INSULATION | | | AND ENERGY CALCULATIONS ARE BASED ON | | | R-19 INSULATION,SEE EPL DISPLAY CARD; | | | CLARIFY | | | | | | 3)SHEET A-3 SHOWS MEAN ROOF HEIGHT OF | | | +17'8",SHEET S-2 LISTS M.R.H.OF 15'-0", | | | DESIGN COMPLIANCE FORM SHOWS 24" AND I | | | CALCULATE IT TO BE +OR- 18'; CLARIFY | | | | | | 4)SHEET S-3 STATES ASCE 7-93 WAS USED | | | FOR CALCULATIONS, THE REFERENCED DESIGN | | | STANDARD FOR USE WITH THE 97 SBC IS ASCE | | | 7-95, WHICH USES WIND LOADS IN EXCESS OF | | | 140 MPH.CLARIFY | | | | | | 5)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | | METRO-DADE PRODUCT APPROVALS FOR STORM | | | PANELS | | | | | | 6)PRODUCT APPROVALS FOR MULLIONS EXPIRED | | | ON 5-1-00. PROVIDE 2 CURRENT COPIES. |
|