2001-01-08 00:00:00CHECKLIST:
 1-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AS PER CITY SAMPLE.
 NOTE: ANCHOR TYPE AND SPACING TO BE
 ACCORDING TO DESIGN PRESSURES, MEAN
 ROOF HEIGHT, STORM PANEL SPAN AND
 STRUCTURE TO BE ATTACHED TO.
 2-ROOF TRUSSES.
 -UPDATE ALL GENERAL DETAILS TO BE
 CONSISTENT WITH SBC 1997 OR ASCE 7-95.
 -DATE AND SIGNATURE OF ENGINEER SHALL
 BE AT THE TIME THE DOCUMENT IS SEALED.
 3-ARCHITECT'S DRAWINGS SHOW "INSWING"
 ENTRY DOORS PROVIDE PRODUCT APPROVAL
 THAT MATCHES THIS INSTALLATION.
 4-PROVIDE ATTIC ACCESS AT MAIN ROOF.
 SECTION 2309.6 SBC 1997.
 5-PROVIDE COMPLETE SPECIFICATIONS FOR
 CONSTRUCTION OF CEILING AT FRONT AND
 REAR PORCHES. SECTION 2504.2 SBC 1997.
  
  
 NOTE: ITEMS ABOVE WERE REQUESTED ON THE
 PROVISO DATED 5-14-00 AND WERE NOT
 DONE OR INCOMPLETE. PLEASE REVIEW
 COMMENTS AND IF THERE IS ANY
 QUESTION PLEASE CALL ME AT
 650-8096 X 8232 FOR CLARIFICATIONS