Plan Review Notes
Plan Review Notes For Permit 00031218
Permit Number 00031218
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DRAINS FOR 2ND.FLOOR CANNOT DISCHARGE
 INTO VENTS FOR 1ST.FLOOR PER SPC 901.2,
 904.1.
  
 CLEARLY SHOW PIPE SIZES FOR ALL STACKS
 AND VENTS.COMPLY W/SPC SEC.714.2,920.2.
  
 NO MORE THAN 2 WATER CLOSETS PERMITTED
 ON 3" BUILDING DRAIN PER TABLE 714.1
 FOOTNOTE #3.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.
  
 MAX.20 FIXTURE UNITS PERMITTED ON 3"
 LINE AT 1/8" PER FT.PER SPC TABLE 714.1.
  
 FIXTURES MISSING ON 2ND.FLR.RISER.