| Plan Review Notes For Permit 00031218 |
| Permit Number |
00031218 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DRAINS FOR 2ND.FLOOR CANNOT DISCHARGE | | | INTO VENTS FOR 1ST.FLOOR PER SPC 901.2, | | | 904.1. | | | | | | CLEARLY SHOW PIPE SIZES FOR ALL STACKS | | | AND VENTS.COMPLY W/SPC SEC.714.2,920.2. | | | | | | NO MORE THAN 2 WATER CLOSETS PERMITTED | | | ON 3" BUILDING DRAIN PER TABLE 714.1 | | | FOOTNOTE #3. | | | | | | WATER CLOSETS AND FIXTURE BRANCHES NOT | | | PERMITTED ON WET VENTS PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.1. | | | | | | MAX.20 FIXTURE UNITS PERMITTED ON 3" | | | LINE AT 1/8" PER FT.PER SPC TABLE 714.1. | | | | | | FIXTURES MISSING ON 2ND.FLR.RISER. |
|