2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE:PLEASE SHOW A/C UNITS ON ELECTRIC
 -AL PLANS AND SHOW THE REQ`D DISCONNECTS
 AND WP GFI OUTLET.440-11/210-63/215-5
  
 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS AND ROOMS
 THAT CAN BE CONVERTED TO SLEEPING ROOMS.
 ALSO REQ`D IN COMMON AREA DOWN MULTI-
 LEVEL DWELLINGS. YOU HAVE THE REQ`D ONE
 FOR UPSTAIRS BUT NEED AN ADDITIONAL ONE
 DOWNSTAIRS. THE ABOVE IS REQ`D BY NFPA-
 72 2-2.1.1.1
  
 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS BEING GFI/GFI
 PROTECTED. AS PER 210-8-A-6
  
 4)NOTE:YOU SHOW ON E-1 200AMP & 100 AMP
 PANEL? THIS DOES NOT CORRELATE WITH E-3
 PLEASE CORRECT. 215-5
  
 5)NOTE;MISSING OUTLET IN 2` OF WALL IN
 BEDROOM. DOWNSTAIRS.
  
 6)NOTE;MISSING OUTLET IN BEDROOM 2` WALL
 UPSTAIRS. 210-52 MASTER BDRM.
  
 7)NOTE:E-3 SHOW METER CAN SIZE.
  
 8)NOTE:AS REQ`D BY 250-50 OF THE NEC.
 BLDG. STEEL MUST BE PART OF THE GROUNDIN
 -G ELECTRODE SYSTEM. PLEASE SHOW
  
 9)NOTE:PLEASE INCLUDE THE REQ`D DEDICATE
 -D BATH(S) CIRCUT(S) PER 210-11-C-3.
 PLEASE SHOW ON PANEL SCHEDULE(S)
  
 10)NOTE:SHOW EACH PANEL LOAD CALCULATION
 ALSO.215-5
 ALSO SHOW IF FEEDERS TO PANELS ARE SLAB.
  
 11)NOTE: PLEASE SHOW THE AIC RATINGS OF
 MAINS.110-9/215-5 MAINS MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
 AIC RATINGS CAN BE FIGURED FROM FAULT
 CURRENT CALCULATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372