| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE:PLEASE SHOW A/C UNITS ON ELECTRIC |
| | -AL PLANS AND SHOW THE REQ`D DISCONNECTS |
| | AND WP GFI OUTLET.440-11/210-63/215-5 |
| | |
| | 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS AND ROOMS |
| | THAT CAN BE CONVERTED TO SLEEPING ROOMS. |
| | ALSO REQ`D IN COMMON AREA DOWN MULTI- |
| | LEVEL DWELLINGS. YOU HAVE THE REQ`D ONE |
| | FOR UPSTAIRS BUT NEED AN ADDITIONAL ONE |
| | DOWNSTAIRS. THE ABOVE IS REQ`D BY NFPA- |
| | 72 2-2.1.1.1 |
| | |
| | 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS BEING GFI/GFI |
| | PROTECTED. AS PER 210-8-A-6 |
| | |
| | 4)NOTE:YOU SHOW ON E-1 200AMP & 100 AMP |
| | PANEL? THIS DOES NOT CORRELATE WITH E-3 |
| | PLEASE CORRECT. 215-5 |
| | |
| | 5)NOTE;MISSING OUTLET IN 2` OF WALL IN |
| | BEDROOM. DOWNSTAIRS. |
| | |
| | 6)NOTE;MISSING OUTLET IN BEDROOM 2` WALL |
| | UPSTAIRS. 210-52 MASTER BDRM. |
| | |
| | 7)NOTE:E-3 SHOW METER CAN SIZE. |
| | |
| | 8)NOTE:AS REQ`D BY 250-50 OF THE NEC. |
| | BLDG. STEEL MUST BE PART OF THE GROUNDIN |
| | -G ELECTRODE SYSTEM. PLEASE SHOW |
| | |
| | 9)NOTE:PLEASE INCLUDE THE REQ`D DEDICATE |
| | -D BATH(S) CIRCUT(S) PER 210-11-C-3. |
| | PLEASE SHOW ON PANEL SCHEDULE(S) |
| | |
| | 10)NOTE:SHOW EACH PANEL LOAD CALCULATION |
| | ALSO.215-5 |
| | ALSO SHOW IF FEEDERS TO PANELS ARE SLAB. |
| | |
| | 11)NOTE: PLEASE SHOW THE AIC RATINGS OF |
| | MAINS.110-9/215-5 MAINS MUST BE RATED |
| | FOR THE AVAILABLE FAULT CURRENT. |
| | AIC RATINGS CAN BE FIGURED FROM FAULT |
| | CURRENT CALCULATIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372 |