| Plan Review Notes For Permit 00031211 |
| Permit Number |
00031211 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNAST ***************** | | | 1)NOTE: SEPARATE LIGHTING FEED TO SEP- | | | -PARATE STUCTURE NOT PERMITTED!. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATING OF NEW | | | EQUIPMENT MAINS. MAIN IS TO BE RATED FOR | | | THE AVAILABLE FAULT CURRENT.110-9/215-5 | | | | | | 3)NOTE: MAINS TO BE GROUPED THIS IS | | | GOING TO DEPEND MAINLY ON NEW TENTS. | | | YOU ARE SHOWING NOW THAT YOU ARE ADDING | | | NEW HOUSE PANEL. THIS SHOULD BE GROUPED | | | AND/OR CLEARLY LABELED AS TO THE LOCATIO | | | -NS OF OTHER MAIN DISC.(EG) 1 OF 2,2OF3 | | | ETC ETC. | | | | | | 4)NOTE: ALL CONTIUOUS LOADS ARE TO BE | | | FIGURED AT 125% (LIGHTING). | | | | | | 5)NOTE: PLEASE SUBMIT PANEL SCHEDULE AND | | | SHOW BRANCH CIRCUT #`S ON PLANS FOR | | | LIGHTING AND ANY BRANCH CIRCUTS. 215-5 | | | | | | 6)NOTE: PLEASE SHOW /LIST EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN DISC TO | | | PANEL AS REQ`D AFTER FIRST MEANS OF DISC | | | ANDSIZE PER 250-122 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. 659-8096 EXT 8372 |
|