Plan Review Notes
Plan Review Notes For Permit 00031205
Permit Number 00031205
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001.TIMOTHY LARGE'S NOTE 4 RELOCATE W.H.
 TO FLOOR OR INSTALL A FIXED LADDER.
 6 1/2 FT OFF FLOOR IS NOT READILY
 ACCESSIBLE.
 2.CONDENSATE FROM A/C AND COOLERS
 CANNOT GO TO SANITARY SEWER SYSTEM.
 CONDENSATE SHOULD GO TO STORM OR TO
 A DRYWELL.
 3.IF NATURAL GAS IS NOT TO BE USED
 REMOVE GAS PIPING DIAGRAM FROM
 SHEET #27.