| 2001-01-08 00:00:00 | 1)CIVIL DRAWING #6-RELOCATE CLEANOUTS |
| | IN STORM SEWER TO ALIGN WITH THE FLOW. |
| | SPC SEC.307.5. |
| | |
| | 2)SHT.FM-1,P-1-MIN.SIZE OF BUILDING |
| | SEWER SHALL BE 4" PER SPC SEC.714.1, |
| | FOOTNOTE #2. |
| | |
| | 3)GREASE TRAP MIN.SIZE SHALL BE 750 GAL. |
| | PER CITY OF WPB ORDINANCE.CANNOT BE |
| | INSIDE FOOD PREP AREA.CONTACT R.COMPO |
| | AT 561-835-7423.SUBMIT APPROVAL FORM |
| | FROM UTILITIES. |
| | |
| | 4)WATER HEATERS SHALL BE READILY |
| | ACCESSIBLE PER SPC SEC.501.7.SUPPLY |
| | FIXED LADDER OR PLATFORM OR RELOCATE |
| | W.H.TO FLOOR. |
| | |
| | 5)RECEPTORS RECEIVING DISCHARGE FROM |
| | INDIRECT WASTES SHALL BE FLOOR SINKS,NOT |
| | FLOOR DRAINS.SPC SEC.804.1,807.1. |
| | |
| | 6)WATER FILTER SYSTEM SHALL BE NSF |
| | APPROVED PER SPC SEC.615.1. |
| | |
| | 7)TRAP PRIMERS FOR FLOOR DRAINS SHALL |
| | COMPLY W/SPC SEC.409.4.1.1. |
| | |
| | 8)DIELECTRIC UNIONS NOT PERMITTED.USE |
| | DIELECTRIC NIPPLES OR COUPLINGS.SPC |
| | 309.3. |
| | |
| | 9)GREASY WASTE SYSTEM SHALL COMPLY W/ |
| | SPC SEC.921 FOR COMBINATION WASTE AND |
| | VENT. |
| | |
| | 10)SEE ATTACHED REQS.FOR GAS INSTALL- |
| | ATION. |
| | |
| | 11)LOCATION AND INSTALLATION OF LP |
| | SYSTEM SHALL COMPLY W/NFPA 58.SHOW SIZE |
| | OF LP TANKS(CAPACITY),LOCATION TO |
| | SOURCES OF IGNITION,BUILDING OPENINGS, |
| | ETC.SEE NFPA 58,TABLE 3-2.2.2., |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |