Plan Review Notes
Plan Review Notes For Permit 00031205
Permit Number 00031205
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED IN
 DESIGN CODE BOX. SHOULD READ NFPA 101-
 LIFE SAFETY CODE, 1985 INSTEAD OF NFPA
 101-LIFE SAFETY CODE, 1994.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 IS TO COMPLY WITH CITY CODE REQUIREMENTS
 3) SERVICE STATION IS TO COMPLY WITH
 THE REQUIREMENTS OF NFPA 30A, THE
 STANDARD FOR AUTOMOTIVE AND MARINE
 SERVICE STATION CODE, AND UNIFORM FIRE
 SAFETY RULES AND STANDARDS, CHAPTER
 4A-49.
 4) THE UNDERGROUND FUEL TANKS ARE TO
 COMPLY WITH NFPA 30, THE STANDARD FOR
 THE STORAGE AND HANDLING OF FLAMMABLE
 AND COMBUSTIBLE LIQUIDS.
 5) PLEASE IDENTIFY TYPE SIGNAGE FOR
 EMERGENCY SHUT OFFS FOR FUEL
 DISPENSING EQUIPMENT.
 6) PLEASE INDICATE ON THE PLANS, THE
 LENGTHS OF FUEL HOSES PLANNED FOR USE.
 7) PLEASE IDENTIFY THE LOCATIONS FOR
 WARNING SIGNS AT THE FUEL DISPENSING
 AREA. WHAT WORDING IS PLANNED FOR THESE
 SIGNS.
 8) PLEASE INDICATE BREAKAWAY DEVICE
 LOCATIONS.
 9) PLEASE INDICATE TYPES AND LOCATIONS
 OF FIRE EXTINGUISHERS.
 10) PROVIDE LISTING INFORMATION ON
 DEVICES PLANNED FOR USE AT FUEL
 DISPENSING AREA.
 11) PLEASE PROVIDE INFORMATION ON
 PROPANE STORAGE AREA.
 12) PLEASE PROVIDE FLAME SPREAD
 CHARACTERISTICS ON CANOPY.
 13) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.