| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED IN |
| | DESIGN CODE BOX. SHOULD READ NFPA 101- |
| | LIFE SAFETY CODE, 1985 INSTEAD OF NFPA |
| | 101-LIFE SAFETY CODE, 1994. |
| | 2) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWINGS. BUILDING ADDRESS |
| | IS TO COMPLY WITH CITY CODE REQUIREMENTS |
| | 3) SERVICE STATION IS TO COMPLY WITH |
| | THE REQUIREMENTS OF NFPA 30A, THE |
| | STANDARD FOR AUTOMOTIVE AND MARINE |
| | SERVICE STATION CODE, AND UNIFORM FIRE |
| | SAFETY RULES AND STANDARDS, CHAPTER |
| | 4A-49. |
| | 4) THE UNDERGROUND FUEL TANKS ARE TO |
| | COMPLY WITH NFPA 30, THE STANDARD FOR |
| | THE STORAGE AND HANDLING OF FLAMMABLE |
| | AND COMBUSTIBLE LIQUIDS. |
| | 5) PLEASE IDENTIFY TYPE SIGNAGE FOR |
| | EMERGENCY SHUT OFFS FOR FUEL |
| | DISPENSING EQUIPMENT. |
| | 6) PLEASE INDICATE ON THE PLANS, THE |
| | LENGTHS OF FUEL HOSES PLANNED FOR USE. |
| | 7) PLEASE IDENTIFY THE LOCATIONS FOR |
| | WARNING SIGNS AT THE FUEL DISPENSING |
| | AREA. WHAT WORDING IS PLANNED FOR THESE |
| | SIGNS. |
| | 8) PLEASE INDICATE BREAKAWAY DEVICE |
| | LOCATIONS. |
| | 9) PLEASE INDICATE TYPES AND LOCATIONS |
| | OF FIRE EXTINGUISHERS. |
| | 10) PROVIDE LISTING INFORMATION ON |
| | DEVICES PLANNED FOR USE AT FUEL |
| | DISPENSING AREA. |
| | 11) PLEASE PROVIDE INFORMATION ON |
| | PROPANE STORAGE AREA. |
| | 12) PLEASE PROVIDE FLAME SPREAD |
| | CHARACTERISTICS ON CANOPY. |
| | 13) GAS INSTALLATION TO COMPLY WITH |
| | NFPA 54. |