| Plan Review Notes For Permit 00031097 |
| Permit Number |
00031097 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: NEED TO SUBMIT NEW LOAD CALCS. | | | PER 220-3-C-1SHOW ALL OF EXISTING SERV- | | | ICE SIZE. | | | 2)NOTE:AS PER 210-8-A-6 NEED TO INDICATE | | | ALL OUTLETS SERVING KITCHEN COUNTER- | | | SPACE AS BEING GFI/GFI PROTECTED. | | | | | | 3)NOTE: AS PER 1996 NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND OUT | | | SIDE ALL SLEEPING ROOMS OF DWELLINGS OF | | | NEW CONSTRUCTION. | | | | | | 4)NOTE: 210-11-C-3 PLEASE LIST NEW BATH | | | CIRCUT REQ`D ON PANEL SCHEDULE. | | | | | | 5)NOTE:PLEASE SHOW NEW LOCATION OF NEW | | | AHU. YOU SHOW NEW A/C COND.UNIT BUT NO | | | AHU. IF IN ATTIC NEEDS LIGHT AND REC. | | | 210-70/21-63 | | | | | | 6)NOTE: YOU SHOW ATTIC ACCESS. AS PER | | | 210-70 NEED TO HAVE LIGHT ON A SWITCH. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|