Plan Review Notes
Plan Review Notes For Permit 00031020
Permit Number 00031020
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: NOTE ENOUGH INFORMATION ON ALL
 LOCATIONS OF EQUIPMENT? PLEASE SHOW
 WHERE MAINS WILL BE GROUPED WITH THE
 EXISTING SERVICE FOR BLDG. 230-72
  
 2)NOTE: PLEASE SHOW LOCATIONS OF EQUIP.
 ON E-1 AND MAINS.,
 SUBMIT AIC RATINGS FOR ALL PANELS AND
 MAIN DISCONNECT BEING INSTALLED. MAINS/
 PANELS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. 110-9
  
 PLEASE SUBMIT ALL THEABOVE INFOMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372