Plan Review Notes
Plan Review Notes For Permit 00030999
Permit Number 00030999
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT REVISED OCCUPANT LOAD
 CALCULATIONS TO ENSURE COMPLIANCE W/SPC
 TABLE 407 FOR MIN.NUMBER OF REQD.
 SANITARY FACILITIES.(ADD'L.LAVS MAY BE
 REQD.)SPC SEC.407.1.3. IS SPECIFIC TO
 THE AREAS ALLOWED TO BE DEDUCTED.
  
 SHT.A-100-SHOW REQD.WHEELCHAIR TURNING
 SPACE IN THE TOILET ROOM AND RESTROOMS
 PER FACBC SEC.4.2.3.
  
 BREAKROOM SINK SHALL COMPLY W/FACBC SEC.
 4.24.1.-4.24.7.
  
 A FLOOR DRAIN IS REQD.IN THE 1ST FLR.
 TOILET ROOM PER SPC SEC.409.4.1.1.
  
 WALLS AND FLOOR IN FIRST FLOOR TOILET
 ROOM SHALL BE NONABSORBENT MATERIAL TO A
 HEIGHT OF 4'PER SPC SEC.1204.2.
  
 URINAL SHALL COMPLY W/FACBC SECS.4.18.1-
 4.18.4.
  
 SHT.A200-TOWEL DISPENSER W/O WASTE SHALL
 COMPLY W/FACBC SEC.4.2.5.,4.2.6 AND FIG.
 6.
  
 SHT.A200-THE LAVS IN THE HANDICAP TOILET
 STALLS SHALL COMPLY W/FACBC SEC.4.17.3.
 (CANNOT INFRINGE ON CLEAR FLOOR SPACE
 FOR WATER CLOSET.)
  
 WATER SOFTENER SHALL BE NSF APPROVED PER
 SPC SEC.615.
  
 SHT.A-220-CAFE EQUIP.SCHEDULE #27 NOTES
 GREASE TRAP IN FLOOR.GREASE TRAP CANNOT
 BE LOCATED IN FOOD PREP AREA PER BOARD
 OF HEALTH REQS.AND CITY ORDINANCE.
  
 SUBMIT WATER SUPPLY RISER PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 RELIEF DRAINS SHALL DISCHARGE TO EXTER-
 IOR PER COUNTYWIDE AMENDMENTS TO SPC SEC
 507.6(3).
  
 SHT.P-3.1-1/2" VENT NOT PERMITTED ON
 GREASY WASTE PER TABLE 920.4.
  
 DESIGN OF CIRCUIT AND LOOP SYSTEM FOR
 RESTROOMS SHALL COMPLY W/SPC SEC.914.
  
 PLANS SHALL BE ROUTED TO DEPT. OF
 BUSINESS REGULATION FOR REVIEW PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
  
  
  
 SUBMIT ENLARGED ARCH.PLAN VIEW AND
 PLUMBING PLAN VIEW FOR THE 1ST.FLR.
 TOILET ROOM PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.