| 2001-01-08 00:00:00 | SUBMIT REVISED OCCUPANT LOAD |
| | CALCULATIONS TO ENSURE COMPLIANCE W/SPC |
| | TABLE 407 FOR MIN.NUMBER OF REQD. |
| | SANITARY FACILITIES.(ADD'L.LAVS MAY BE |
| | REQD.)SPC SEC.407.1.3. IS SPECIFIC TO |
| | THE AREAS ALLOWED TO BE DEDUCTED. |
| | |
| | SHT.A-100-SHOW REQD.WHEELCHAIR TURNING |
| | SPACE IN THE TOILET ROOM AND RESTROOMS |
| | PER FACBC SEC.4.2.3. |
| | |
| | BREAKROOM SINK SHALL COMPLY W/FACBC SEC. |
| | 4.24.1.-4.24.7. |
| | |
| | A FLOOR DRAIN IS REQD.IN THE 1ST FLR. |
| | TOILET ROOM PER SPC SEC.409.4.1.1. |
| | |
| | WALLS AND FLOOR IN FIRST FLOOR TOILET |
| | ROOM SHALL BE NONABSORBENT MATERIAL TO A |
| | HEIGHT OF 4'PER SPC SEC.1204.2. |
| | |
| | URINAL SHALL COMPLY W/FACBC SECS.4.18.1- |
| | 4.18.4. |
| | |
| | SHT.A200-TOWEL DISPENSER W/O WASTE SHALL |
| | COMPLY W/FACBC SEC.4.2.5.,4.2.6 AND FIG. |
| | 6. |
| | |
| | SHT.A200-THE LAVS IN THE HANDICAP TOILET |
| | STALLS SHALL COMPLY W/FACBC SEC.4.17.3. |
| | (CANNOT INFRINGE ON CLEAR FLOOR SPACE |
| | FOR WATER CLOSET.) |
| | |
| | WATER SOFTENER SHALL BE NSF APPROVED PER |
| | SPC SEC.615. |
| | |
| | SHT.A-220-CAFE EQUIP.SCHEDULE #27 NOTES |
| | GREASE TRAP IN FLOOR.GREASE TRAP CANNOT |
| | BE LOCATED IN FOOD PREP AREA PER BOARD |
| | OF HEALTH REQS.AND CITY ORDINANCE. |
| | |
| | SUBMIT WATER SUPPLY RISER PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | RELIEF DRAINS SHALL DISCHARGE TO EXTER- |
| | IOR PER COUNTYWIDE AMENDMENTS TO SPC SEC |
| | 507.6(3). |
| | |
| | SHT.P-3.1-1/2" VENT NOT PERMITTED ON |
| | GREASY WASTE PER TABLE 920.4. |
| | |
| | DESIGN OF CIRCUIT AND LOOP SYSTEM FOR |
| | RESTROOMS SHALL COMPLY W/SPC SEC.914. |
| | |
| | PLANS SHALL BE ROUTED TO DEPT. OF |
| | BUSINESS REGULATION FOR REVIEW PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 |
| | |
| | |
| | |
| | SUBMIT ENLARGED ARCH.PLAN VIEW AND |
| | PLUMBING PLAN VIEW FOR THE 1ST.FLR. |
| | TOILET ROOM PER COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.104.2.1. |