| Plan Review Notes For Permit 00030999 |
| Permit Number |
00030999 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR MAIN AND EACH PANEL. | | | | | | 2)NOTE: SUBMIT AIC RATINGS OF ALL MAINS | | | AND RATINGS OF BRANCH BRKRS. PER 110-9 | | | | | | 3)NOTE; NEED TO SUBMIT LINE DIAGRAM OF | | | SERVICE .TO INCLUDECONDUITS, WIRE SIZE | | | COMPLETE GROUNDING SYSTEM. | | | | | | 4)NOTE: SUBMIT PANEL SCHEDULES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|