| Plan Review Notes For Permit 00030957 |
| Permit Number |
00030957 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | MAIN. MAINS ARE TO BE RATED FOR THE | | | AVAILABLE FAULT CURRENT PER 110-9/215-5 | | | PLEASE SHOW. | | | | | | 2)NOTE: BLDG.STEEL MUST BE PART OF THE | | | GROUNDING ELECTRODE SYSTEM. 250-50 | | | PLEASE SHOW. 215-5 | | | | | | 3)NOTE: PLEASE NOTE THAT ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED.210-8-A-6 THIS INCLUDE | | | -S BREAKFAST AREA. | | | | | | 4)NOTE: CHECK FOR 2` OF WALL IN KITCHEN | | | AREA 210-52 AND ALSO OUTLET FOR KITCHEN | | | HALL EITHER 2` RULE OR HALL REQ`MENT | | | 210-52H | | | | | | PLANS WOULD HAVE PASSED WITH PROVISO | | | AND RED LINES BUT AIC RATINGS MUST BE ON | | | ALL PLANS. | | | PLEASE SUBMIT THE ABOVE FOR REIVEW. IF | | | THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|