| Plan Review Notes For Permit 00030941 |
| Permit Number |
00030941 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1]1997 FL.ACC.CODE REQUIRES ACCESSIBLE | | | PARKING.ACCESSIBLE ENTRANCE SHALL BE | | | THE PRIMARY NOT THE SECONDARY[SEE RAMP | | | AT REAR]. | | | 2]CERTIFY ADDITIONAL FLOOR LOADING,FROM | | | RESIDENTIAL TO BUSINESS USE.SEE TABLE | | | 1604.1,STANDARD BUILDING CODE. | | | 3]SUBMIT PRODUCT TESTING ON ALL NEW EXT. | | | WINDOWS AND DOORS. | | | 4]EXPLAIN NOTE ON SHEET A.2"APPLIED | | | HURRICANE SHUTTERS". | | | 5]SUBMIT PALM BEACH COUNTY IMPACT RECEIP |
|