| Notes |
| Date |
Text |
| 2001-02-28 00:00:00 | NOTE:MINIMUM OF 10' BETWEEN INTAKE AND | | | EXHAUST OPENINGS. | | | | | | FAN SHUT DOWN BY DUCT SMOKE | | | DETECTOR REQUIRED WITH NOTIFI- | | | CATION TO HORN/STROBE IN OCCUPIED | | | AREAS, AS PER NFPA 90A 4-4.4.3. | | | OPERATION TO BE TESTED BEFORE | | | FINAL C.O. | | | | | | IS THE WALL RATED BETWEEN FELLOW- | | | SHIP HALL AND HALLWAY TOWARDS THE | | | LIBRARY?IF SO, FIRE DAMPER | | | REQUIRED.ALSO, ACOUSTICAL | | | CEILING JUST IN FELLOWSHIP HALL | | | OR INTO THE HALLWAY?ACCESS- | | | IBILITY TO AHU'S. |
|