2001-02-28 00:00:00NOTE:MINIMUM OF 10' BETWEEN INTAKE AND
 EXHAUST OPENINGS.
  
 FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR REQUIRED WITH NOTIFI-
 CATION TO HORN/STROBE IN OCCUPIED
 AREAS, AS PER NFPA 90A 4-4.4.3.
 OPERATION TO BE TESTED BEFORE
 FINAL C.O.
  
 IS THE WALL RATED BETWEEN FELLOW-
 SHIP HALL AND HALLWAY TOWARDS THE
 LIBRARY?IF SO, FIRE DAMPER
 REQUIRED.ALSO, ACOUSTICAL
 CEILING JUST IN FELLOWSHIP HALL
 OR INTO THE HALLWAY?ACCESS-
 IBILITY TO AHU'S.