| 2001-01-08 00:00:00 | 1)SUBMIT APPROVAL FROM CITY OF WEST PALM | | | BEACH UTILITIES FOR GREASE TRAP.CONTACT | | | R.COMPO AT 561-835-7423. | | | | | | 2)SUBMIT DETAIL OF GREASE TRAP.SEE | | | ATTACHED. | | | | | | 3)SIZING OF GAS PIPE TO RANGE SHALL | | | COMPLY W/TABLE 305.4(A).LOAD SHALL BE | | | BASED ON 70'FROM FURTHEST OUTLET. | | | | | | 4)A UNION IS REQD.DOWNSTREAM OF THE SHUT | | | OFF VALVES PER NFPA 54,SEC.5.5.2. | | | | | | 5)SHOW LOACTION OF AUTOMATIC SHUTOFF | | | VALVE (FIRE VALVE)ON GAS LINE PER NFPA | | | 96,SEC.7-4. | | | | | | 6)MIN.SIZE DRAIN U/G SHALL BE 2" PER | | | SPC SEC.714.4. | | | | | | 7)SUBMIT CALCULATIONS FOR STORM DRAIN- | | | AGE SYSTEM.SHOW SQ.FT.AREA DRAINED BY | | | EACH DRAIN,AND INCLUDE 1/2 THE AREA OF | | | PARAPET WALLS TO THE HORIZONTAL PROJECT- | | | ION.SUBMIT CALCULATIONS FOR SECONDARY | | | DRAINAGE.SIZE PER SPC SEC.1109.3 AND | | | APPENDIX "A". | | | | | | NOTE:PLEASE PUT THESE PLANS TOGETHER IN | | | AN ORDERLY MANNER AND SUBMIT 2 COMPLETE | | | SETS. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|