Plan Review Notes
Plan Review Notes For Permit 00030836
Permit Number 00030836
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)SUBMIT APPROVAL FROM CITY OF WEST PALM
 BEACH UTILITIES FOR GREASE TRAP.CONTACT
 R.COMPO AT 561-835-7423.
  
 2)SUBMIT DETAIL OF GREASE TRAP.SEE
 ATTACHED.
  
 3)SIZING OF GAS PIPE TO RANGE SHALL
 COMPLY W/TABLE 305.4(A).LOAD SHALL BE
 BASED ON 70'FROM FURTHEST OUTLET.
  
 4)A UNION IS REQD.DOWNSTREAM OF THE SHUT
 OFF VALVES PER NFPA 54,SEC.5.5.2.
  
 5)SHOW LOACTION OF AUTOMATIC SHUTOFF
 VALVE (FIRE VALVE)ON GAS LINE PER NFPA
 96,SEC.7-4.
  
 6)MIN.SIZE DRAIN U/G SHALL BE 2" PER
 SPC SEC.714.4.
  
 7)SUBMIT CALCULATIONS FOR STORM DRAIN-
 AGE SYSTEM.SHOW SQ.FT.AREA DRAINED BY
 EACH DRAIN,AND INCLUDE 1/2 THE AREA OF
 PARAPET WALLS TO THE HORIZONTAL PROJECT-
 ION.SUBMIT CALCULATIONS FOR SECONDARY
 DRAINAGE.SIZE PER SPC SEC.1109.3 AND
 APPENDIX "A".
  
 NOTE:PLEASE PUT THESE PLANS TOGETHER IN
 AN ORDERLY MANNER AND SUBMIT 2 COMPLETE
 SETS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.