| Plan Review Notes For Permit 00030836 |
| Permit Number |
00030836 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | 1.PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89 | | | 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3.NO ROOFTOP DRAWING INDICATING LOCATION | | | OF RTU'S AND EXHAUST FAN TERMINATION AND | | | REQUIRED DISTANCE FROM EACH OTHER | | | 4. IF EXHAUST FANS WORK WITH LIGHT | | | SWITCH PER A/C 1, THEY CAN NOT BE USED | | | AS PART OF THE AIR BALANCE SCHEDULE REQ- | | | UIRED IN NOTE 2. |
|