Plan Review Notes
Plan Review Notes For Permit 00030836
Permit Number 00030836
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89
 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2
 3.NO ROOFTOP DRAWING INDICATING LOCATION
 OF RTU'S AND EXHAUST FAN TERMINATION AND
 REQUIRED DISTANCE FROM EACH OTHER
 4. IF EXHAUST FANS WORK WITH LIGHT
 SWITCH PER A/C 1, THEY CAN NOT BE USED
 AS PART OF THE AIR BALANCE SCHEDULE REQ-
 UIRED IN NOTE 2.