Plan Review Notes
Plan Review Notes For Permit 00030836
Permit Number 00030836
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001-LOAD CALCULATION IS NO DONE IN ACCORDA
 WITH THE CODE
 1- LIGHTING LOADS ARE FIGURED PER ART.
 220-3A FOR SERVICE CALCS.
 2- IF USING THE FIXTURES THEY ARE FIGU
 USING THE HIGHEST AMPERAGE ON BALST
 NOT BULB SIZE.THEN THEY HAVE TO B
 A LARGER LOAD THAN 220-3A WOULD BE
 3- POWER OUTLETS ARE FIGURED AT 180VA
 PER EACH BUT I CAN ONLY COUNT 57 OF
 THEM.
 4- CONTINUOUS LOAD FACTORS AND MOTOR
 CONTRIBUTION IS NOT SHOWN ALSO!
 2- MAINS ARE TO BE GROUPED AND LABELED!!