| Plan Review Notes For Permit 00030836 |
| Permit Number |
00030836 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1-LOAD CALCULATION IS NO DONE IN ACCORDA | | | WITH THE CODE | | | 1- LIGHTING LOADS ARE FIGURED PER ART. | | | 220-3A FOR SERVICE CALCS. | | | 2- IF USING THE FIXTURES THEY ARE FIGU | | | USING THE HIGHEST AMPERAGE ON BALST | | | NOT BULB SIZE.THEN THEY HAVE TO B | | | A LARGER LOAD THAN 220-3A WOULD BE | | | 3- POWER OUTLETS ARE FIGURED AT 180VA | | | PER EACH BUT I CAN ONLY COUNT 57 OF | | | THEM. | | | 4- CONTINUOUS LOAD FACTORS AND MOTOR | | | CONTRIBUTION IS NOT SHOWN ALSO! | | | 2- MAINS ARE TO BE GROUPED AND LABELED!! |
|