| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | 2ND REVIEW | | | ---------- | | | | | | PLEASE REFER TO ORIGINAL COMMENTS DATED | | | MAY 1,2000[COPY ATTACHED] | | | | | | 1]COMPIANCE WITH SBC TABLE 500 ALLOWABLE | | | BUILDING AREA HAS NOT BEEN PROVIDED. | | | LETTER FROM ENGINEER DATED 7/31/00 | | | CALLS FOR EXISTING WALL TO BE MODIFIED | | | TO 4HR CONSTRUCTION.FIRST VERIFY THAT | | | CLASS B-4 BLOCK EXIST,THEN EXPLAIN | | | WHAT THE CELLS WILL BE FILLED WITH AND | | | HOW THIS WILL BE PERFORMED. | | | 2]OK | | | 3]OK | | | 4]INFORMATION REQUESTED HAS NOT BEEN | | | PROVIDED. | | | 5]SUBMIT STORM SHUTTER TEST REPORTS. | | | 6]INFORMATION REQUESTED HAS NOT BEEN | | | PROVIDED. | | | | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 561-659-8096#8456 |
|