| Plan Review Notes For Permit 00030836 |
| Permit Number |
00030836 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVAL REQD.FROM CITY OF WPB UTILITIES | | | FOR GREASE TRAP.CONTACT R.COMPO OR | | | B.KAMP AT 561-835-7423.SUBMIT APPROVAL | | | FORM FROM UTILITIES. | | | | | | MIN.REQD.SANITARY FACILITIES SHALL | | | COMPLY W/SPC SEC.407.1.3.OCCUPANT LOAD | | | FOR HALL AND CLASSROOMS REQD.TO ENSURE | | | COMPLIANCE W/TABLE 407. | | | | | | MOP DRAIN NOT SHOWN ON FLOOR PLAN & CAN | | | WASH & MOP DRAIN NOT PROPERLY VENTED. | | | SPC SEC.901.2. | | | | | | D.W.CANNOT DISCHARGE INTO GREASE INTER- | | | CEPTOR PER CITY OF WPB ORDINANCE. | | | | | | DISHWASHER SHALL COMPLY W/SPC SEC. | | | 409.1.2. | | | | | | DRINKING FOUNTAINS REQD.AMOUNT SHALL | | | COMPLY W/SPC TABLE 407. | | | | | | SUBMIT DETAIL OF GREASE TRAP.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | SIZING OF GAS PIPE TO RANGE SHALL COMPLY | | | W/SGC TABLE 305.4(A). | | | | | | AUTOMATIC SHUT-OFF VALVE (FIRE VALVE)AND | | | UNION REQD.UPSTREAMOF GAS EQUIPMENT | | | PER NFPA 96,SEC.7-4,NFPA 54 SEC.5.5.4. | | | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPD SEC.409.4.1.1. |
|