| 2001-01-08 00:00:00 | **************PROVISO ***************** | | | | | | 1)NOTE: SHOW ALL MEANS OF EGRESS LIGHT-N | | | -ING. 210-70 | | | | | | 2)NOTE:SHOW RECEPT ON ROOF REQ`D FOR | | | A/C 210-63. | | | | | | 3)NOTE: ON E-1 FOR KITCHEN EXHAUST YOU | | | SHOW 180 HP? PLEASE CORRECT. | | | | | | 4)NOTE:PLEASE NOTE ART 362-4 FOR SIZING | | | OF WIREWAY FOR 600 MCM | | | | | | 5)NOTE: PLEASE SHOW THE BREAK DOWN ON | | | THE LOAD CALCULATION. PLEASE SHOW THE | | | CONTINUOUS LOADS (LIGHTING ETC) FIGURED | | | AT 125% PER 210-20 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. THE PLANS WOULD HAVE PASSED WITH | | | A PROVISO BUT WERE COMING BACK FOR PLUMB | | | CORRECTIONS. PLEASE MAKE THE ELECTRICAL | | | CHANGES. IF THERE ARE ANY QUESTIONS CALL | | | 659-8096 EXT 8372 |
|