| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-REVISE/UPDATE SEE COMMENTS ON PLANS. |
| | 2-REVISE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. MEAN |
| | ROOF HEIGHT IS INCORRECT. MEAN ROOF |
| | HEIGHT IS 19'-8" PLUS OR MINUS. MEAN |
| | ROOF HEIGHT IS TAKEN FROM GRADE, NOT |
| | FROM FINISH FLOOR, TO THE AVERAGE |
| | POINT OF THE HIGHEST ROOF. |
| | 3-PROVIDE PRODUCT APPROVAL FOR SLIDING |
| | GLASS DOORS WITH TRANSOM ABOVE |
| | ASSEMBLY, ARCHED WINDOWS. |
| | 4-REVISE TRUSS ANCHOR SCHEDULE TO RESIST |
| | THE UPLIFT LOADS CALCULATED ON THE |
| | ENGINEERED TRUSSES. FOR EXAMPLE SEE |
| | TRUSS FG1. CHECK ALL OTHERS AS WELL. |
| | 5-PROVIDE THE DESIGN PRESSURES AT ALL |
| | EXTERIOR OPENINGS. |
| | 6-PROVIDE SURVEY WITH BUILDING LAYOUT. |
| | 7-STORM PANELS: |
| | -INSTALLATION SCHEDULE AND KEY PLAN TO |
| | MATCH PLANS FOR 4 BEDROOMS LAYOUT. |
| | -CLEARLY IDENTIFY MOUNTING CONDITIONS |
| | AND ANCHORS AND SPACING TO BE USED. |
| | 8-CLARIFY WHO IS THE STRUCTURAL ENGINEER |
| | FOR THIS HOUSE. THE SITE SPECIFIC |
| | PRODUCT APPROVAL IS SIGNED AND SEALED |
| | BY ONE ENGINEER. THE DESIGN |
| | CERTIFICATION FOR BUILDING CODE |
| | COMPLIANCE IS SIGNED AND SEALED BY |
| | ANOTHER ENGINEER. BUT, NEITHER OF |
| | THESE ENGINEERS SIGNED AND SEALED THE |
| | STRUCTURAL DRAWINGS. |