Plan Review Notes
Plan Review Notes For Permit 00030794
Permit Number 00030794
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
  
 1)NOTE:NEED TO RE-FIG LOAD CALCULATIONS
 PER ART 220-20 OF THE NEC. ALSO LIGHTING
 MUST BE SHOWN AT 125% AND THE LARGEST
 MOTOR LOAD. 125 % FOR CONTINUOUS LOADS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. THE PLANS WOULD HAVE PASSED WITH
 A PROVISO BUT WERE COMING BACK FOR
 PLUMB COMMENTS ANYWAY. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372