| Plan Review Notes For Permit 00030730 |
| Permit Number |
00030730 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE:SHOW A/C EQUIPMENT ON ELEC PALNS | | | TO INCLUDE OUTSIDE COND.W/DISC 440-11 | | | NEED TO SHOW THE SIZE OF EXISTING MAIN. | | | 215-5 NEED TO SUBMIT REVISED RISER/AND | | | PANEL SCHEDULES. | | | | | | 2)NOTE: NEED TO SHOW ON PANEL SCHEDULE | | | THE REQ`D DEDICATED CIRCUT FOR BATH(S) | | | AS PER 210-11-C-3/215-5 | | | | | | 3)NOTE: NEED TO SHOW ALL SMOKE DETECTORS | | | REQ`D BY NFPA-72 2-2.1.1.1 INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS AND ROOMS | | | THAT MAY BE CONVERTED INTO SLEEPING | | | ROOMS,(LIKE THE STUDIO). | | | SMOKE DETETORS ARE REQ`D FOR BOTH FLOORS | | | IN A COMMON AREA. | | | | | | | | | 4)NOTE: YOU SHOW ON YOUR LOAD CALCULAT- | | | -ION EXISTING SQ.FT? PLEASE INCLUDE NEW | | | SQ FOOTAGE YOU ARE ADDING IF NOT ALREADY | | | 220-3-C-1 | | | | | | 5)NOTE: PLEASE CHECK THE REQ`D OUTLET | | | SPACING PER 210-522`6`12` RULE. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|