Plan Review Notes
Plan Review Notes For Permit 00030730
Permit Number 00030730
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:SHOW A/C EQUIPMENT ON ELEC PALNS
 TO INCLUDE OUTSIDE COND.W/DISC 440-11
 NEED TO SHOW THE SIZE OF EXISTING MAIN.
 215-5 NEED TO SUBMIT REVISED RISER/AND
 PANEL SCHEDULES.
  
 2)NOTE: NEED TO SHOW ON PANEL SCHEDULE
 THE REQ`D DEDICATED CIRCUT FOR BATH(S)
 AS PER 210-11-C-3/215-5
  
 3)NOTE: NEED TO SHOW ALL SMOKE DETECTORS
 REQ`D BY NFPA-72 2-2.1.1.1 INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS AND ROOMS
 THAT MAY BE CONVERTED INTO SLEEPING
 ROOMS,(LIKE THE STUDIO).
 SMOKE DETETORS ARE REQ`D FOR BOTH FLOORS
 IN A COMMON AREA.
  
  
 4)NOTE: YOU SHOW ON YOUR LOAD CALCULAT-
 -ION EXISTING SQ.FT? PLEASE INCLUDE NEW
 SQ FOOTAGE YOU ARE ADDING IF NOT ALREADY
 220-3-C-1
  
 5)NOTE: PLEASE CHECK THE REQ`D OUTLET
 SPACING PER 210-522`6`12` RULE.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372