Plan Review Notes
Plan Review Notes For Permit 00030713
Permit Number 00030713
Review Stop P
Sequence Number 5
Notes
Date Text
2001-01-08 00:00:00CLEARLY SHOW THE LENGTH AND WIDTH OF THE
 HANDICAP TOILET STALLS IN THE TOILET
 ROOMS.COMPLY W/FACBC SEC.4.17.3.
  
 LAYOUT OF TOILET ROOM #110 ON SHT.P-2
 DOESN'T MATCH SHEETS A-1,A-2.
  
 THE TOILET STALL IN ROOM #110 DOESN'T
 COMPLY W/FACBC.IF A STALL IS GOING TO BE
 UTILIZED IT MUST COMPLY W/FACBC SEC.
 4.17.3.
  
 AN ADDITIONAL H.C .STALL IS REQD.IN THE
 WOMEN'S RESTROOM PER FACBC SEC.4.22.4.
  
 FIXTURES DOWNSTREAM OF WATER CLOSETS
 SHALL BE VENTED PER SPC SEC.913.2.
 (SEE ROOM #101)
  
 RISER #6/P-2 DOESN'T MATCH 3/P-2.
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 MAKE ALL CHANGESFROM ORIGINAL PLANS
 ON REVISED SET.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1