Plan Review Notes
Plan Review Notes For Permit 00030713
Permit Number 00030713
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 OF PANELS INCLUDING ALL CONTINUOUS
 LOADS AT 125% (LIGHTING ETC )
  
 THIS WAS ASKED FOR ON THE FIRST TWO
 REVIEWS. PLEASE SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 EXT
 8372