| Plan Review Notes For Permit 00030713 |
| Permit Number |
00030713 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT THE AVERAGE DAILY ATTENDANCE | | | FOR THE EDUCTIONAL AREA PER TABLE 407 OF | | | SPC. | | | | | | ALL PUBLIC AND COMMON USE TOILET ROOMS | | | SHALL COMPLY W/FACBC SEC.4.22 PER FACBC | | | SEC.4.1.3(11).SEE ROOMS #110,111. | | | | | | CLEARLY SHOW DIMENSIONS (LXW) OF H.C. | | | STALLS.COMPLY W/FACBC SEC.4.17.3(NEW | | | CONSTRUCTION.) | | | | | | SHT.A-2-SHOW CLEAR FLOOR SPACE UNDER | | | DRINKING FOUNTAIN.(GENERAL REFERENCE OR | | | NOTE TO CODE IS UNACCEPTABLE PER COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.104.2.1. | | | | | | FLOOR DRAINS SHALL BE EQUIPPED W/TRAP | | | PRIMERS PER SPC SEC.409.4.1.1. | | | | | | SUBMIT SANITARY AND WATER RISER DIAGRAMS | | | FOR SNACK SHOP AREA AND DETAIL TYPE OF | | | ITEMS TO BE SOLD/DISTRIBUTED AT THIS | | | AREA.APPROVAL FROM DEPT.OF BUSINESS MAY | | | BE REQD. | | | | | | DESIGN OF THE SANITARY SYSTEM SHALL | | | COMPLY W/SPC SEC.906.2.1.THE DRAWING | | | (PLAN VIEW AND ISOMETRIC STILL SHOW THE | | | VENTS OFFSETTING HORIZONTALLY BELOW THE | | | SLAB.) | | | | | | SHT.P-2- WATER CLOSETS NOT PERMITTED ON | | | WET VENTS PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.911.1.1.CONNECT W.C.'S TO STACK. |
|