2001-01-08 00:00:00SUBMIT THE AVERAGE DAILY ATTENDANCE
 FOR THE EDUCTIONAL AREA PER TABLE 407 OF
 SPC.
  
 ALL PUBLIC AND COMMON USE TOILET ROOMS
 SHALL COMPLY W/FACBC SEC.4.22 PER FACBC
 SEC.4.1.3(11).SEE ROOMS #110,111.
  
 CLEARLY SHOW DIMENSIONS (LXW) OF H.C.
 STALLS.COMPLY W/FACBC SEC.4.17.3(NEW
 CONSTRUCTION.)
  
 SHT.A-2-SHOW CLEAR FLOOR SPACE UNDER
 DRINKING FOUNTAIN.(GENERAL REFERENCE OR
 NOTE TO CODE IS UNACCEPTABLE PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 FLOOR DRAINS SHALL BE EQUIPPED W/TRAP
 PRIMERS PER SPC SEC.409.4.1.1.
  
 SUBMIT SANITARY AND WATER RISER DIAGRAMS
 FOR SNACK SHOP AREA AND DETAIL TYPE OF
 ITEMS TO BE SOLD/DISTRIBUTED AT THIS
 AREA.APPROVAL FROM DEPT.OF BUSINESS MAY
 BE REQD.
  
 DESIGN OF THE SANITARY SYSTEM SHALL
 COMPLY W/SPC SEC.906.2.1.THE DRAWING
 (PLAN VIEW AND ISOMETRIC STILL SHOW THE
 VENTS OFFSETTING HORIZONTALLY BELOW THE
 SLAB.)
  
 SHT.P-2- WATER CLOSETS NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.CONNECT W.C.'S TO STACK.