Plan Review Notes
Plan Review Notes For Permit 00030713
Permit Number 00030713
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00MINIMUM NUMBER OF TOILET FACILITIES
 SHALL COMPLY W/SPC SEC.407.1.3.AND TABLE
 407.
  
 SUBMIT U.L.ASSEMBLY NUMBERS FOR FIRE
 SAFING DETAILS SHOWN ON A-3.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.4.
  
 ALL PUBLIC AND COMMON AREA TOILET ROOMS
 SHALL COMPLY W/FACBC SECS.4.1.3(11),
 4.22.
  
 HANDICAP STALLS SHALL COMPLY W/FACBC
 SEC.4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION)4.1.6.(B).
  
 SHT.A-2-CLEAR FLOOR SPACE UNDER H.C.
 LAV.SHALL BE 29" PER FACBC SEC.4.19.2.
  
 SHT.A-2-CLEAR FLOOR SPACE UNDER DRINKING
 FOUNTAINS SHALL COMPLY W/FACBC SEC.
 4.15.5.
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).
  
 PIPES UNDER LAVS.SHALL COVERED PER FACBC
 SEC.4.19.4.
  
 RM.111-STALL DOOR INFRINGES ON CLEAR
 FLOOR SPACE FOR URINAL.COMPLY W/FACBC
 4.18.3,4.22.2.
  
 WALLS IN TOILET ROOMS SHALL BE
 NONABSORBENT TO A HEIGHT OF 4' PER SBC
 SEC.1204.2.
  
 TOILET ROOMS SHALL BE EQUIPPED W/FLOOR
 DRAINS PER SPC SEC.409.4.1.1.
  
 HEIGHT OF COUNTER IN EMPLOYEE LOUNGE
 SHALL COMPLY W/FACBC SEC.4.2.5,4.2.6.&
 FIGS.#5 & 6.
  
 VENTS FOR WATER CLOSETS IN ROOMS #115 &
 116 SHALL COMPLY W/FACBC SEC.905.2.1.
 (BASE MUST BE WASHED BY A FIXTURE)
  
 SIZE ALL SECTIONS OF THE SANITARY RISERS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 DOMESTIC WATER RISER SHOWS 1-1/4" LINE
 SUPPLYING A 2" LINE.CLARIFY.