| 2001-01-08 00:00:00 | MINIMUM NUMBER OF TOILET FACILITIES |
| | SHALL COMPLY W/SPC SEC.407.1.3.AND TABLE |
| | 407. |
| | |
| | SUBMIT U.L.ASSEMBLY NUMBERS FOR FIRE |
| | SAFING DETAILS SHOWN ON A-3.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.4. |
| | |
| | ALL PUBLIC AND COMMON AREA TOILET ROOMS |
| | SHALL COMPLY W/FACBC SECS.4.1.3(11), |
| | 4.22. |
| | |
| | HANDICAP STALLS SHALL COMPLY W/FACBC |
| | SEC.4.17.3(SEE EXCEPTION:NEW |
| | CONSTRUCTION)4.1.6.(B). |
| | |
| | SHT.A-2-CLEAR FLOOR SPACE UNDER H.C. |
| | LAV.SHALL BE 29" PER FACBC SEC.4.19.2. |
| | |
| | SHT.A-2-CLEAR FLOOR SPACE UNDER DRINKING |
| | FOUNTAINS SHALL COMPLY W/FACBC SEC. |
| | 4.15.5. |
| | |
| | DRINKING FOUNTAINS SHALL COMPLY W/FACBC |
| | SEC.4.1.3(10)(A). |
| | |
| | PIPES UNDER LAVS.SHALL COVERED PER FACBC |
| | SEC.4.19.4. |
| | |
| | RM.111-STALL DOOR INFRINGES ON CLEAR |
| | FLOOR SPACE FOR URINAL.COMPLY W/FACBC |
| | 4.18.3,4.22.2. |
| | |
| | WALLS IN TOILET ROOMS SHALL BE |
| | NONABSORBENT TO A HEIGHT OF 4' PER SBC |
| | SEC.1204.2. |
| | |
| | TOILET ROOMS SHALL BE EQUIPPED W/FLOOR |
| | DRAINS PER SPC SEC.409.4.1.1. |
| | |
| | HEIGHT OF COUNTER IN EMPLOYEE LOUNGE |
| | SHALL COMPLY W/FACBC SEC.4.2.5,4.2.6.& |
| | FIGS.#5 & 6. |
| | |
| | VENTS FOR WATER CLOSETS IN ROOMS #115 & |
| | 116 SHALL COMPLY W/FACBC SEC.905.2.1. |
| | (BASE MUST BE WASHED BY A FIXTURE) |
| | |
| | SIZE ALL SECTIONS OF THE SANITARY RISERS |
| | PER COUNTYWIDE AMENDMENTS TO SPC SEC. |
| | 104.2.1. |
| | |
| | DOMESTIC WATER RISER SHOWS 1-1/4" LINE |
| | SUPPLYING A 2" LINE.CLARIFY. |