Plan Review Notes
Plan Review Notes For Permit 00030713
Permit Number 00030713
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PANEL SCHEDULES NOT COMPLETE.??
 NEED TO SHOW MDP.E-2 IS MISSING LC AND
 IS SHOWING MDP??
 2)NOTE: NEED TO SUBMIT COMPLETE POWER
 RISER DIAGRAM.YOU ARE MISSING LC
  
 3)NOTE: ALSO SUBMIT THE AIC RATINGS OF
 MDP/MAIN.110-9 /215-5
  
 4)NOTE: MISSING LOAD CALCULATIONS??
 NEED TO SUBMIT LOAD CALCS AND INCLUDING
 CONTIUOUS LOADS SUCH AS LIGHTING.215-5
  
  
 PLEASE SUBMIT THE ABOVE INFROMATION FOR
 REIVEW. IF THERE ARE ANY QUESTIONS PLEAS
 CALL.659-8096 EXT 8372


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved