| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PANEL SCHEDULES NOT COMPLETE.?? | | | NEED TO SHOW MDP.E-2 IS MISSING LC AND | | | IS SHOWING MDP?? | | | 2)NOTE: NEED TO SUBMIT COMPLETE POWER | | | RISER DIAGRAM.YOU ARE MISSING LC | | | | | | 3)NOTE: ALSO SUBMIT THE AIC RATINGS OF | | | MDP/MAIN.110-9 /215-5 | | | | | | 4)NOTE: MISSING LOAD CALCULATIONS?? | | | NEED TO SUBMIT LOAD CALCS AND INCLUDING | | | CONTIUOUS LOADS SUCH AS LIGHTING.215-5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFROMATION FOR | | | REIVEW. IF THERE ARE ANY QUESTIONS PLEAS | | | CALL.659-8096 EXT 8372 |
|