| Plan Review Notes For Permit 00030500 |
| Permit Number |
00030500 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | 1)PROVIDE SOIL TEST REPORT PRIOR TO 1ST | | | INSPECTION | | | | | | 2)PROVIDE 2 CURRENT COPIES OF PRODUCT | | | APPROVALS FOR STORM PANELS | | | | | | 3)NOTE 2 SHEET A-5 SPECIFIES R-30 | | | CEILING INSULATION AND THE ENERGY CALCS | | | SHOW R-19 CEILING INSULATION. CLARIFY & | | | CORRECT. | | | | | | 4)NOTES ON SHEET A 5-3 REFER TO ASCE7-93 | | | THE CORRECT REFERENCE STANDARD FOR 97SBC | | | IS ASCE7-95. WIND LOADS CAN BE CALCULAT- | | | ED USING ASCE7-95 OR 97SBC 1606,BUT THEY | | | CAN NOT BE MIXED,SEE 1606.1.2. |
|