| Plan Review Notes For Permit 00030458 |
| Permit Number |
00030458 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | **************DENIED******************** | | | 1) ENCLOSURE DOES NOT COMPLY WITH 1997 | | | SMC 505.9. THE ENCLOSURE SHALL BE USED | | | EXCLUSIVELY TO ENCLOSE A SINGLE GREASE | | | EXHAUST SYSTEM AND SHALL BE USED FOR NO | | | OTHER PURPOSE. | | | 2) EXHAUST TERMINATION SHALL BE LOCATED | | | MIN. 10 FT. FROM ANY ADJACENT BUILDING, | | | PROPERTY LINE, WINDOW, DOOR, PARKING | | | AREA OR AIR INTAKE OPENING PER 1997 SMC | | | 506.1 | | | 3) PROVIDE INFORMATION ON AREA WHERE | | | SMALLER HOOD TERMINATES. ALSO EXHAUST | | | FAN APPEARS TO BE CONNECTED TO SUPPLY | | | DUCT | | | | | | PROVIDE PLANS SHOWING CORRECTION OF | | | ABOVE LISTED ITEMS FOR REVIEW |
|