Plan Review Notes
Plan Review Notes For Permit 00030458
Permit Number 00030458
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00 
 **************DENIED********************
 1) ENCLOSURE DOES NOT COMPLY WITH 1997
 SMC 505.9. THE ENCLOSURE SHALL BE USED
 EXCLUSIVELY TO ENCLOSE A SINGLE GREASE
 EXHAUST SYSTEM AND SHALL BE USED FOR NO
 OTHER PURPOSE.
 2) EXHAUST TERMINATION SHALL BE LOCATED
 MIN. 10 FT. FROM ANY ADJACENT BUILDING,
 PROPERTY LINE, WINDOW, DOOR, PARKING
 AREA OR AIR INTAKE OPENING PER 1997 SMC
 506.1
 3) PROVIDE INFORMATION ON AREA WHERE
 SMALLER HOOD TERMINATES. ALSO EXHAUST
 FAN APPEARS TO BE CONNECTED TO SUPPLY
 DUCT
  
 PROVIDE PLANS SHOWING CORRECTION OF
 ABOVE LISTED ITEMS FOR REVIEW