| Plan Review Notes For Permit 00030458 |
| Permit Number |
00030458 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************DENIED********************** | | | | | | 1)1997 SMC 505.9 REQUIRES ENCLOSURE FOR | | | EXHAUST DUCT PROVIDE DETAIL FOR ENCLOSUR | | | INCLUDING REQUIRED 6 INCHES MINIMUN | | | CLEARANCE BETWEEN DUCT AND INTERIOR | | | SURFACE OF THE ENCLOSURE | | | 2)HOOD AND EXHAUST DUCT SYSTEM SHALL | | | HAVE NOT LESS THAN 18 INCHES CLEARANCE | | | FROM COMBUSTIBLE CONSTRUCTION 1997 SMC | | | 505.12 | | | 3) EXHAUST TERMINATION SHALL BE LOCATED | | | 10FT MIN. FROM ANY ADJACENT BUILDING, | | | PROPERTY LINE, WINDOW, DOOR, PARKING | | | AREA OR AIR INTAKEOPENING PER 1997 | | | SMC 506.1 | | | 4) PROVIDE INFORMATION ON AREA WHERE | | | SMALLER HOOD TERMINATES. ALSO EXHAUST | | | FAN APPEARS CONNECTED TO SUPPLY DUCT |
|