2001-01-08 00:00:00************DENIED**********************
  
 1)1997 SMC 505.9 REQUIRES ENCLOSURE FOR
 EXHAUST DUCT PROVIDE DETAIL FOR ENCLOSUR
 INCLUDING REQUIRED 6 INCHES MINIMUN
 CLEARANCE BETWEEN DUCT AND INTERIOR
 SURFACE OF THE ENCLOSURE
 2)HOOD AND EXHAUST DUCT SYSTEM SHALL
 HAVE NOT LESS THAN 18 INCHES CLEARANCE
 FROM COMBUSTIBLE CONSTRUCTION 1997 SMC
 505.12
 3) EXHAUST TERMINATION SHALL BE LOCATED
 10FT MIN. FROM ANY ADJACENT BUILDING,
 PROPERTY LINE, WINDOW, DOOR, PARKING
 AREA OR AIR INTAKEOPENING PER 1997
 SMC 506.1
 4) PROVIDE INFORMATION ON AREA WHERE
 SMALLER HOOD TERMINATES. ALSO EXHAUST
 FAN APPEARS CONNECTED TO SUPPLY DUCT