Plan Review Notes
Plan Review Notes For Permit 00030426
Permit Number 00030426
Review Stop Z
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO". PROVIDE ELEVATION
 CERTIFICATE.
 2-CLEARLY INDICATE WINDOWS TO HAVE
 SAFETY GLAZING AS PER SECTION 2405.2
 SBC 1997. SEE PLANS FOR COMMENTS.
 3-REVISE ENERGY CALCULATIONS TO REFLECT
 THE ACTUAL AREA UNDER THE ATTIC. SEE
 SECTION 602.1.ABC.1.2 FLORIDA ENERGY
 CODE, 1997 EDITION.
 4-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY AND
 PRODUCT APPROVAL FOR EXTERIOR FRENCH
 DOOR IN MASTER SUITE.
 5-STORM PANELS:
 -CLARIFY WHY THE INSTALLATION SCHED.
 SPECIFIES ANCHOR SPACING TO BE 12" OC,
 WHILE ANCHOR SCHEDULE ON SHEET 6 OF 15
 OF APPROVED DRAWINGS IS HIGHLIGHTED
 DIFFERENTLY.
 -CLEARLY INDICATE WHICH STORM PANELS
 ARE GOING TO BE INSTALLED IN CONCRETE
 AND WHICH ONES ON MASONRY.
 6-REVISE/UPDATE ALL DRAWINGS AS REQUIRED
 SEE COMMENTS ON PLANS.