2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO". PROVIDE ELEVATION
 CERTIFICATE.
 2-CLEARLY INDICATE WINDOWS TO HAVE
 SAFETY GLASS. SECTION 2405.2 SBC 1997.
 3-REVISE ENERGY CALCULATIONS:
 -FLOOR AREA UNDER ATTIC TO BE INCREASED
 AS REQUIRED. SEE SECTION 602.1.ABC.1.2
 FLORIDA ENERGY CODE, 1997 EDITION.
 4-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE ASSEMBLY AND FOR
 EXTERIOR FRENCH DOOR AT MASTER SUITE.
 5-STORM PANELS:
 -CLARIFY WHY THE INSTALLATION SCHEDULE
 SPECIFIES ANCHOR SPACING TO BE 12" OC,
 WHILE, ANCHOR SCHEDULE ON SHEET 6 OF
 15 OF APPROVED DRAWINGS IS BEING
 HIGHLIGHTED DIFFERENTLY.
 -CLEARLY SPECIFY WHICH STORM PANELS ARE
 GOING TO BE INSTALLED IN CONCRETE AND
 WHICH ARE GOING TO BE INSTALLED ON
 MASONRY. NOTICE THE DIFFERENCE ON
 ANCHOR SPACING.
 6-REVISE/UPDATE ALL PLANS AS REQUIRED.
 SEE COMMENTS ON PLANS.