| 2001-01-08 00:00:00 | DRAIN FROM TOWER SHALL DISCHARGE TO AN | | | APPROVED POINT OF DISPOSAL WHERE DAMAGE | | | TO BUILDING,OCCUPANTS OR CONTENTS WILL | | | NOT OCCUR.SPC SEC.301.2.THIS DRAIN | | | CANNOT DISCHARGE TO THE DRAINAGE SYSTEM | | | INSIDE THE BUILDING. | | | | | | DATA SHALL BE SUBMITTED FOR THE PH OF | | | THE EFFLUENT FROM THE COOLING TOWER. | | | COMPLY W/SPC SEC.801.4. | | | | | | MAKE-UP WATER LINES SHALL BE PROTECTED | | | AGAINST BACKFLOW PER SPC SEC.606.1. |
|