2001-01-08 00:00:00DRAIN FROM TOWER SHALL DISCHARGE TO AN
 APPROVED POINT OF DISPOSAL WHERE DAMAGE
 TO BUILDING,OCCUPANTS OR CONTENTS WILL
 NOT OCCUR.SPC SEC.301.2.THIS DRAIN
 CANNOT DISCHARGE TO THE DRAINAGE SYSTEM
 INSIDE THE BUILDING.
  
 DATA SHALL BE SUBMITTED FOR THE PH OF
 THE EFFLUENT FROM THE COOLING TOWER.
 COMPLY W/SPC SEC.801.4.
  
 MAKE-UP WATER LINES SHALL BE PROTECTED
 AGAINST BACKFLOW PER SPC SEC.606.1.