Plan Review Notes
Plan Review Notes For Permit 00030296
Permit Number 00030296
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: NEED TO PROVIDE AIC RATING OF
 EQUIPMENT MAIN. PER NEC 110-9/215-5
 MAINS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
  
 PLEASE SUBMIT FOR REVIEW AND APPROVAL
 BEFORE ROUGH INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372