Plan Review Notes
Plan Review Notes For Permit 00030264
Permit Number 00030264
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE AS REQ`D BY 230-72/
 AND 225-32 NEED TO HAVE MAINS GROUPED
 AND MAIN COMING INTO STUCURE MUST HAVE
 MEANS OF DISC.
  
 2)NOTE: ALSO PLEASE SUBMIT AIC RATINGS
 OF MAINS/ YOU SHOW FUSE DISC.PLEASE LIST
 THEIR AIC RATING ON DRAWINGS.110-9/215-5
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 561-659-8096 EXT 8372