| Plan Review Notes For Permit 00030224 |
| Permit Number |
00030224 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | KITCHEN SINK NOT PROPERLY VENTED.SPC SEC | | | 901.2. | | | | | | SHOWER/TUBS ON 2ND.FLR.NOT PROPERLY | | | VENTED.SPC 901.2. | | | | | | WATER CLOSET IN MASTER BATH EXCEEDS | | | DISTANCE FROM VENT PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.908.1,FOOTNOTE#2. | | | | | | FIXTURES DOWNSTREAM OF WATER CLOSETS | | | SHALL BE VENTED PER SPC SEC.913.2 |
|