| Plan Review Notes For Permit 00030224 |
| Permit Number |
00030224 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING OF THE | | | EQUIPMENT MAINS. MAIN MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT, 110-9 | | | | | | 2)NOTE: NEED TO INCLUDE THE BLDG. STEEL | | | AS PART OF THE GROUNDINGELECTRODE | | | SYSTEM AS PER 250-50 | | | | | | 3)NOTE: NEED TO HAVE THE REQ`D DEDICATED | | | BATH(S) CIRCUT(S) AS PER 210-11-C-3 | | | NEED TO BE #12 AND 20AMP. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|