2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF THE
 EQUIPMENT MAINS. MAIN MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT, 110-9
  
 2)NOTE: NEED TO INCLUDE THE BLDG. STEEL
 AS PART OF THE GROUNDINGELECTRODE
 SYSTEM AS PER 250-50
  
 3)NOTE: NEED TO HAVE THE REQ`D DEDICATED
 BATH(S) CIRCUT(S) AS PER 210-11-C-3
 NEED TO BE #12 AND 20AMP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372