Plan Review Notes
Plan Review Notes For Permit 00030212
Permit Number 00030212
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE PROFESSIONAL SURVEY SHOWING
 BUILDING LAYOUT. SIGNED, SEALED AND
 DATED.
 2-PROVIDE COMPLETE INSTALLATION DETAIL
 OF WINDOWS AT BREAKFAST AREA THAT ARE
 ATTACHED TO STEEL COLUMN.
 3-FOOTING F2:
 -PROVIDE DETAIL SHOWING THE WIDTH AND
 DEPTH DIMENSIONS.
 NOTE: 16" MIN. DEPTH AS PER SECTION
 1804.1.3 SBC 1997 AND MINIMUM WIDTH OF
 16" AS PER SOIL TEST REPORT.
 4-REVISE DESIGN CERTIFICATION FOR BLDG
 CODE COMPLIANCE FORM:
 -MEAN ROOF HEIGHT IS 18'-6" PLUS OR
 MINUS. MEAN ROOF HEIGHT IS TAKEN FROM
 GRADE, NOT FROM FINISH FLOOR, TO THE
 AVERAGE POINT OF HIGHEST ROOF.
 -CLARIFY WHY IS THERE ANOTHER ENGINEER
 SEALING THIS FORM BUT HE IS NOT
 SEALING THE STRUCTURAL PLANS.
 5-SEE COMMENTS ON PLANS AND REVISE AND
 UPDATE ALL PLANS AS REQUIRED.
 NOTE: ARCHITECT NEEDS TO DATE ALL
 DRAWINGS AT TIME OF STAMPING HIS SEAL.
 6-PROVIDE PRODUCT APPROVAL FOR OVAL AND
 ARCHED WINDOWS, SLIDING GLASS DOORS
 WITH TRANSOM ABOVE COMPLETE ASSEMBLY.
 NOTE: PRODUCT APPROVAL FOR RECTANGULAR
 WINDOWS DOESN'T INCLUDE ROUND, OVAL OR
 ARCHED WINDOWS.
 7-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC. 1606 SBC 1997.
 8-SPECIFY CEILING CONSTRUCTION AT FRONT
 AND REAR PORCHES. SPECIFY FASTENERS
 AND SPACING.SEC. 2504.2 SBC 1997.
 9-TRUSS ANCHOR SCHEDULE IS NOT LEGIBLE.
 10-ROOF TRUSSES:
 -REVISE MEAN ROOF HEIGHT.18'-6".
 -THERE ARE SOME ROOF TRUSSES DESIGNED
 AT 16'-0" AND SOME AT 23'-0". THERE
 IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 11-STORM PANELS:
 -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR SPACING TO BE USED.