| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1) REFRIGERANT LEAK DETECTION AND VENTI- | | | LATION FANS ARE LIFE SAFETY COMPONENTS | | | OF THE BUILDING SYSTEM AND REQUIRE | | | CONNECTION TO THE EMERGENCY POWER SYSTEM | | | 2) INTERIOR NOTIFICATION OF REFIGERANT | | | LEAK TO BE BY HORN AND STROBE AND TO BE | | | INITIATED AT TIME OF EXTERIOR NOTIFICA- | | | TION |
|