| Date |
Text |
| 2001-01-08 00:00:00 | 1)PLANS SHALL BE APPROVED BY CITY OF |
| | WEST PALM BEACH ENGINEERING DEPT.FOR THE |
| | WATER SEWER,AND STORM DRAINAGE.COUNTY- |
| | WIDE AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | 2)SUBMIT COPIESOF APPROVALS FROM P.B. |
| | COUNTY HEALTH DEPT.AND DEP,(NOT INCLUDED |
| | W/RESPONSE SHEET.)COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.101.4.7 |
| | |
| | 3)FLOOR DRAINS SHALL BE INSTALLED SO |
| | INLET IS AT ALL TIMES IN FULL VIEW.SEE |
| | F.D.IN 1ST.FLR.VENDING AREA.SPC SEC. |
| | 409.4.1.2. |
| | |
| | 4)SUBMIT COMPLETE GAS ISOMETRIC FOR |
| | REVIEW.SHOW TYPE OF PIPING,ALL CUT |
| | SECTIONS OF PIPE,DISTANCE TO MOST REMOTE |
| | OUTLET,BTU LOAD OF EACH APPLIANCE,TOTAL |
| | LOAD ON SYSTEM.SUBMITAPPLICABLE |
| | SIZING TABLE USED T0 DESIGN THE SYSTEM. |
| | |
| | 5)SUBMIT DETAIL OF OIL INTERCEPTOR FOR |
| | ELEVATOR SUMP AND PUMP.VENTS SHALL |
| | COMPLY W/SPC SEC.906.2.1. |
| | |
| | 6)SANITARY SYSTEM REQUIRES ONE MAIN VENT |
| | THROUGH THE ROOF.(DOES NOT APPEAR TO BE |
| | ON THE PLANS.) |
| | |
| | 7)SHT.P-4-VENTS FOR TUBS SHALL COMPLY W/ |
| | SPC SEC.906.2.1.(THEY SHALL BE A MIN.OF |
| | 6"ABOVE THE FLOOD LEVEL RIM OF THE |
| | FIXTURE BEFORE OFFSETTING HORIZONTALLY.) |
| | |
| | 8)VENT STACKS FOR WASTE AND SOIL STACKS |
| | SHALL COMPLY W/SPC 906.2.2, 918. |
| | |
| | 9)KITCHEN STACK DIAGRAM-FIXTURES SHALL |
| | DISCHARGE TO GREASY WASTE,NOT TO |
| | SANITARY PER SPC SEC.1004.1, 1004.4. |
| | DRY VENTS NOT PERMITTED. |
| | |
| | 10)SHT.P-4.3-TUBS,W.C.'S AND SHOWERS |
| | SHALL COMPLY W/SPC SEC.906.2.2.(VENTS) |
| | |
| | 11)DESIGNAND CAPACITY OF GREASE TRAP |
| | SHALL BE APPROVED BY CITY OF WEST PALM |
| | UTILITIES.CALL R.COMPO AT (561)835-7423 |
| | SUBMIT COPY OF APPROVAL FORM FROM |
| | UTILITIES. |
| | |
| | 12)DESIGN OF CONDENSATE SYSTEM SHALL |
| | COMPLY W/SPC 304.8.3,304.8.4. OF SMC. |
| | |
| | 13)SUBMIT DETAILS ON GAS VENTS.SHOW |
| | TERMINATION POINTS.COMPLY W/SGC SEC. |
| | 608. |
| | |
| | 14)SIZING OF BRANCH VENT FOR 1ST.FLR. |
| | TOILET ROOM SHALL COMPLY W/SPC TABLE |
| | 920.4. |
| | |
| | 15)ALL ADDENDUMS SHALL BE DRAWN ON FULL |
| | SHEETS AND SIGNED AND SEALED PER FLA. |
| | STATUTE. |
| | |
| | 16)A LINT INTERCEPTOR IS REQUIRED FOR |
| | THE DISCHARGE FROM THE LAUNDRY ROOMS.SPC |
| | SEC.1004.11 |
| | |
| | 17)THE GREASE TRAP SHALL COMPLY W/ |
| | CITY OF WEST PALM BEACH UTILITIES. |
| | TWO WAY CLEANOUTS ARE REQD.ON THE INLET |
| | AND OUTLET DRAIN LINES,AND MANHOLES ARE |
| | REQD.ON THE INLET AND OUTLET. |
| | |
| | 18)WATER SUPPLY BRANCHES TO THE ROOMS |
| | SHALL BE VALVED PER SPC SEC.610.4.1. |
| | |
| | 19)A WELL DRILLING PERMIT IS REQD.FROM |
| | DEP FOR THE WELL AND A WATER USE PERMIT |
| | IS REQD. FROM SFWMD FOR THE IRRIGATION |
| | SYSTEM PER FLA.STATUTE 373.219. |