| 2001-01-08 00:00:00 | *************DENIED********************* |
| | |
| | 1)PROVIDE INFORMATION ON EXHAUST DUCT |
| | RISER MATERIAL |
| | 2)KITCHEN HOOD AND EXHAUST DUCT WILL RE- |
| | QUIRE SEPARATE PERMIT AND MORE DETAILED |
| | PLANS |
| | 3)PROVIDE OUTSIDE AIR CALCULATIONS PER |
| | ASHRAE 62-89 |
| | 4)PROVIDE AIR BALANCE SCHEDULE PER 1997 |
| | SMC 501.2 |
| | 5)1997 SMC 304.8.6.1 REQUIRES SECONDARY |
| | DRAIN LINE TO BE RUN SEPARATELY FROM |
| | PRIMARY CONDENSATE DRAIN LINE |
| | 6)PROVIDE DETAIL FOR PROTECTION OF DRYER |
| | VENT IN RATED WALL |
| | 7)1997 SMC 610.6 REQUIRES SPECIFIC LOCA- |
| | TION AND INSTALLATION DETAILS FOR EACH |
| | FIRE DAMPER, FIRE DOOR, ETC. TO BE SHOWN |
| | AND PROPERLY IDENTIFIED ON THE BUILDING |
| | PLANS BY THE DESIGNER. THE FOLLOWING |
| | LOCATIONS DO NOT INDICATE FIRE DAMPERS |
| | M2.1 2-18X12 THRU RATED WALLS 2 PLACES |
| | 2-14X12 THRU RATED MEETING ROOM |
| | WALLS |
| | 2-12X8 THRU MEN'S AND WOMEN'S ROOM |
| | RATED WALLS |
| | NO FIRE DAMPERS AT COMBUSTION AIR |
| | OPENING |
| | 2-18X10 IN RATED MAINTANANCE ROOM |
| | WALL |
| | PROVIDE DETAIL FOR FIRE PROTECTION OF |
| | OPENING @ 14" FLUE PIPE PENETRATING |
| | RATED WALL BY WATER HEATER ROOM |
| | M2-2 FIVE DUCTS LEAVING MECH ROOM 217 |
| | ON 2ND FLOOR PLAN NO FIRE DAMPERS SHOWN |
| | M2-3 10X8 R/A DUCT @ STORAGE ROOM 318A |
| | RATED WALL |
| | 10X8 R/A DUCT @ RM 320 RATED WALL |
| | M2-4 12X8 R/A DUCT @ RM 418 AND RM 420 |
| | |
| | SEPARATE PERMITS AND PLANS WILL BE |
| | REQUIRED FOR WALK IN COOLERS/FREEZERS, |
| | KITCHEN HOOD, FIRE SUPPRESSION SYSTEM |