| Plan Review Notes For Permit 00030112 |
| Permit Number |
00030112 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1-PAGES E1.2,E1.3,E1.4 ALL SHOW PANELS | | | MOUNTED IN THE LINEN STORAGE ROOM SEE | | | SECTIONS 240-24D, AND 384-7 WHY THEY | | | CAN NOT BE LOCATED THERE! | | | | | | 2-PAGE E4.2 SHOWS A PANEL LABLED "PE" | | | HOW IS THIS FED AND IT SHOWS NO LOADS | | | OTHER THAN LIGHTING.ALSO THIS IS IN | | | A SEPARATE STRUCTURE PLEASE TREAT AS | | | PER CODE. | | | | | | 3-NO LOAD FOR "PE" SHOWN IN LOAD | | | CALCULATION PLEASE CHECK | | | | | | 4-FAULT CURRENT RATING NEEDED FOR ALL | | | SERVICE AND DISTRIBUTION EQUIPMENT!!! | | | 110-9,10 |
|